Electrical Work at the Bridger Plant Materials Center, Bridger, Montana
Archived on March 18, 2026. Original response deadline: . Full description on SAM.gov.
Description
Please see Attaachment 1 Statement of Work for further detailed description of services.
This work is for the United States Department of Agriculture - Natural Resources Conservation
Service (NRCS) Bridger Plant Materials Center (PMC), located at 98 South River Rd., Bridger, MT
59014-9718. The work is to run three-phase power from the main distribution panel to a subpanel, to
power an existing outlet for charging a forklift and to install a new connection for the new
walk-in seed cooler.
The Contractor shall:
Install conduit on the exterior of the building from the main distribution panel (MDP) unit to the
interior wall behind the walk-in cooler, an approximate distance of 65 feet (from the 100amp panel
to the disconnect of the cooler is a total of 25 feet). The exterior wall is tin with insulation
and osb/plywood; interior walls are tin with insulation. Install a 100amp three-phase service feed
from the MDP to a new 100amp three-phase panel located next to the existing electric forklift
receptacle. Conduit raceway will be metal EMT and Wire conductors will be copper THHN.
Remove the forklift breaker from the outdoor MDP and install a new 100amp Three Phase breaker in
place. Re-feed the forklift disconnect out of the new 100amp sub panel to the existing forklift
receptable, installing new solid conduit, wiring, and receptacle if required. Subpanel is 3 feet
from the forklift.
Provide for electrical wiring of the Walk-in Cooler. Install a surface mount conduit from the new
Three Phase sub panel to the Walk-in Cooler area. Install a service disconnect switch for the
Walk-in
Cooler. Wire from the service disconnect to the already pre-wired control panel located on the
Walk-in Cooler. Note: Start up and testing of the Walk-in Cooler to be done by a separate HVAC
Contractor provided by the owner.
Dispose or recycle all materials removed from the site. Clean all spaces associated with the work.
Timely completion of deliverables is essential to a successful outcome. All work must be completed
within 30 calendar days of the contract being awarded.
All the materials and work required and performed by the contractors must be warrantied for one
year
from the date of completion of the project.
Overview
Award Overview
Possible prior contracts
Sign in to see possible prior contracts for this requirement (matched by agency, NAICS and place of performance; not confirmed).
Contacts
Contracting Officer
Primary Contact
Documents
Showing 5 of 5 items
Document | Source | Agency | Posted Date | File Size | Actions | |
|---|---|---|---|---|---|---|
| Combined Synopsis/Solicitation | FARM PRODUCTION AND CONSERVATION BUSINESS CENTER | Feb 17, 2026 | 192.88 KB | |||
| Combined Synopsis/Solicitation | FARM PRODUCTION AND CONSERVATION BUSINESS CENTER | Feb 17, 2026 | 146.68 KB | |||
| Combined Synopsis/Solicitation | FARM PRODUCTION AND CONSERVATION BUSINESS CENTER | Feb 17, 2026 | 72.7 KB | |||
| Combined Synopsis/Solicitation | FARM PRODUCTION AND CONSERVATION BUSINESS CENTER | Feb 17, 2026 | 14.15 KB | |||
| Combined Synopsis/Solicitation | FARM PRODUCTION AND CONSERVATION BUSINESS CENTER | Feb 17, 2026 | 19.61 KB |
Lifecycle
12FPC326Q0002- Combined Synopsis
- Combined SynopsisCurrentFeb 17, 2026
Electrical Work at the Bridger Plant Materials Center, Bridger, Montana
Similar Opportunities
Title | Phase | Agency | NAICS | Set Aside | Posted | Deadline | Location |
|---|---|---|---|---|---|---|---|
Additional Details
Solicitation Number
12FPC326Q0002
Archive Date
Mar 18, 2026
Office Address
WASHINGTON, DC, 20250