Mechanical
· Install (3) indoor wall-mounted units, along with all refrigerant and drain piping.
· Install (1) 6-ton heat pump. Unit to be anchored to exterior concrete wall via on L-bracket steel frame.
· Coordinate core penetrations through concrete wall for piping, electrical, and drain lines. Installation to
include all wall waterproofing.
· Provide and insulate all refrigerants and condensate piping above ceiling
· Test and charge system to verify operation.
Electrical
· Install new dedicated 208V, 3-phase power circuit
· Provide NEMA 4X, 60A non-fused stainless steel disconnect at outdoor unit
· Provide power and control conduit and wiring to/from all units
· Penetrate concrete wall.
· Provide penetration and conduit through roof deck. Patch and flash roof as required to maintain new roof
warranty through Carlisle Roof installer.
Controls
· Integrate mini-split system into the existing FAA Schneider Electric EcoStruxure DDC system via BACnet
· Provide and install one IP-IO module at VAV-17 for coordinated backup cooling enable/disable
· Submit point list, graphics, and control narrative to COR for approval.
· Program unit set points, and update AHU-3 supply air setpoints
· Support commissioning of system to validate operation.
Structural & Interior
· Concrete core penetration for pipes and conduits
· Provide support framing for all units and steel plates as shown in drawing.
· Provide support for pipes and conduits.
· Work to include wall restoration and painting.
Showing 5 of 5 items
Document | Source | Agency | Posted Date | File Size | Actions | |
|---|---|---|---|---|---|---|
| Solicitation | FEDERAL AVIATION ADMINISTRATION | Mar 4, 2026 | 36.12 KB | |||
| Solicitation | FEDERAL AVIATION ADMINISTRATION | Mar 4, 2026 | 39.34 KB | |||
| Solicitation | FEDERAL AVIATION ADMINISTRATION | Mar 4, 2026 | 1.41 MB | |||
| Solicitation | FEDERAL AVIATION ADMINISTRATION | Mar 4, 2026 | 725.26 KB | |||
| Solicitation | FEDERAL AVIATION ADMINISTRATION | Mar 4, 2026 | 924 KB |
TSS_Ductless_System_at_EWR_ATCT
Apr 30, 2026
FORT WORTH, TX, 76177
TSS_Ductless_System_at_EWR_ATCTNotice ID: b688b6a803724b1a95ae03855fc87037
Notice ID: 19e399a7c066432aa1da8d87bf61788a
Notice ID: c8d08fdf07b34b848f4d9fb91dcf463a