J041--Cooling Tower Controller Replacement
Awarded on July 3, 2023. Full description on SAM.gov.
Awarded tounder 36C24123P0882 (source: SAM.gov award notice)• $543.0K
Overview
- Posted
- July 11, 2023
- Notice type
- Award Notice
- Set-aside
- Service-Disabled Veteran-Owned Small Business (SDVOSB) Set-Aside (FAR 19.14)
Notice details
- Place of performance
- See PWS.
- Last updated
- Dec 4, 2025
- Award date
- Jul 3, 2023
- Award amount (SAM.gov award notice)
- $543.0K
Identifiers
- Solicitation number
- 36C24123Q0689
- Notice ID
- 49ebeb4b2220498f9edd99cef31f4a43
- Award number (PIID)
- 36C24123P0882
Description
** AMENDMENT A00001 Cooling Tower Controller Replacement and Maintenance West Haven VAMC Contractor Site Visit Questions and Government Responses ** Please confirm receipt of this amendment in your solicitation response How long have the absorbers been dormant and have they been tested to insure they function properly now? Units are currently being brought online to test for functionality. Service reports are available from Joel C./Plant Supervisor. Service work is being provided by Broad this week (week of June 5th) to setup the building 19/ CHP Plant s chilled water system for the cooling season. Per work on Tuesday, June 6, 2023, basket strainers were found to be plugged and have been cleaned. Building 19 chilled water system (chillers, cooling towers) will be exercised before end of week to assess and improve flow and improve operational efficiency as required. Board has provided past pre and post cooling season services for the building 19/ CHP Plant in August 2021, Oct 2022, April 2022, and July 2022. What process (if any) was used to put the absorbers into long term storage? Long term storage was performed by Broad USA the manufacture of absorber. What documentation was done with putting the absorbers into long term storage and does the VA (or a Contractor) have this documentation? See answers to question #1. Is there any documentation on the condition of the bromide and/or has the bromide been tested in the past or recently? BRASCO In August of 2022 conducted a checks and test of the Cooling Tower and Bromide for quality and/or biological record on file in CHP Plant. Have the chiller tubes been punched or have Eddy Currents been performed? The chiller tubes have not been punched. Board checked but did not punch. Per the check this week, flow through absorption cooling unit deemed to be OK. Full system operation/flow is scheduled before end of this week. See answer to question #1. Is there currently water in the chiller barrels? It will be filled by end of the week of June 5th. If so, has that water been tested in the past or recently? N/A Are there original start-up sheets available for the absorbers? Yes (on the HDMI). Board s O&M Manual(s) available on site and/or through vendor. Does the warranty being asked for in the bid document refer to labor, equipment or bot. Equipment
Award Overview
Award Number
36C24123P0882
Award Amount (SAM.gov award notice)
$543.0K
Award Date
Jul 3, 2023
Awardee
Awardee UEI
CADSMUE9J2M4
Awardee CAGE Code
8HBD7
Original Solicitation
Notice ID: 49ebeb4b2220498f9edd99cef31f4a43
Posted Date: Jul 11, 2023
Original Response Deadline: Not specified
More From This Vendor
Top 5 most recent
- $5.2MSigned Oct 28, 2026
- $322.0KSigned Oct 27, 2026
- $120.3KSigned Sep 16, 2026
- $112.6KSigned Sep 15, 2026
- $293.7KSigned Sep 11, 2026
Contacts
Documents
No documents available.
Lifecycle
Solicitation:
36C24123Q0689- Combined Synopsis
- Awarded
This opportunity has been awarded.
- 2×Combined SynopsisMay 31, 2023
J041--Cooling Tower Controller Replacement & Maintenance SDVOSB Set Aside
- AwardedCurrentJul 11, 2023
J041--Cooling Tower Controller Replacement
Similar Opportunities
Title | Match | Phase | Deadline |
|---|---|---|---|
Additional Details
Solicitation Number
36C24123Q0689
Archive Date
Aug 10, 2023
Office Address
TOGUS, ME, 04330