Notice ID: a41197163765401490a21b0b29a2b017Combined Synopsis/Solicitation
6120--RFQ - Brand Name or Equal to ELECTRICAL TRANSFORMER
Archived on March 16, 2025. Original response deadline: . Full description on SAM.gov.
Overview
- Response deadline
- 4:00 PM UTC−05:00
- Posted
- January 7, 2025
- Notice type
- Combined Synopsis/Solicitation
- Set-aside
- Total Small Business Set-Aside (FAR 19.5)
Notice details
- Office
- 242-NETWORK CONTRACT OFFICE 02 (36C242)
- Place of performance
- St. Albans VA Medical Center 179-00 Linden Boulevard, Queens, NY, 11424
- Last updated
- Jan 23, 2026
Identifiers
- Solicitation number
- 36C24225Q0217
- Notice ID
- a41197163765401490a21b0b29a2b017
Description
To facilitate its mission, the New York Harbor Healthcare System Engineering Office requires the purchase of an electrical transformer for building 89 at the St. Albans VA Medical Center. After a power failure, the St. Albans VA Medical Center has been renting a Daelim Belefic 500kVA 4160 / 207Y / 120v three-phase radial feed pad-mount transformer until a transformer can be procured.
Award Overview
Possible prior contract
Inferred, not confirmedInferred, not confirmed. Matched by agency, NAICS, place of performance and end-date proximity. This is a candidate, not the contractor of record.
Vendor
ELEMCO SERVICES, INC.Contract end date
Feb 19, 2025
NAICS
335311
Agency
Department of Veterans Affairs
Dollar amounts are not shown for inferred matches because the link is heuristic. Open the award below to check it.
Contacts
Documents
Select documents to download
Showing 4 of 4 items
Document | Source | Agency | Posted Date | File Size | Actions | |
|---|---|---|---|---|---|---|
| Sources Sought | VETERANS AFFAIRS, DEPARTMENT OF | Jan 7, 2025 | - | |||
| Combined Synopsis/Solicitation | VETERANS AFFAIRS, DEPARTMENT OF | Jan 7, 2025 | - | |||
| Combined Synopsis/Solicitation | VETERANS AFFAIRS, DEPARTMENT OF | Jan 7, 2025 | - | |||
| Combined Synopsis/Solicitation | VETERANS AFFAIRS, DEPARTMENT OF | Jan 7, 2025 | - |
Lifecycle
Solicitation:
36C24225Q0217- Market Research
- Combined Synopsis
- Market ResearchDec 26, 2024
6120--Sources Sought - ELECTRICAL TRANSFORMER
- Combined SynopsisCurrentJan 7, 2025
6120--RFQ - Brand Name or Equal to ELECTRICAL TRANSFORMER
Similar Opportunities
Title | Match | Phase | Deadline |
|---|---|---|---|
1000 KVA TRANSFORMER | 75% | Combined Synopsis | 09/30/2026 |
73% | Awarded | Open | |
Pad Mount Transformer | 73% | Combined Synopsis | 08/31/2026 |
Provide one Pad Mounted Transformer 750 kVA, 13.2 kV /208Y/120 V. Salient Characteristics: Furnish one (1) pad mounted, dead front, radial transformer, rated: ? Capacity: 750 kVA ? Phases: 3 ? Primary Voltage: 13,200 V (15 kV class) ?Secondary Voltage: 208Y/120 V ? Frequency: 60 Hz ? Phase: Three phase ? Cooling :ONAN ? Fluid: Mineral oil 2. Mandatory Physical Dimensions: The following dimensions are non negotiable: ? Height: 63? inches (up to 64? inches) ? Width: 65 inches ? Depth: May varies (existing is 41 inches) The Contractor shall confirm with proposal the manufacturing dimensions, either in writing or by a shop drawing, for government approval. 3. Mechanical and Construction Requirements: The transformer shall include: ?Stainless steel tank, cabinet and hardware (304) ? Dead front construction ? Pentahead security hardware ? ANSI 61 Grey color to match with existing enclosure ? Welded tank construction, sealed and pressure tested ? 1-inch Oil drain valve located on the primary side with 3/8-inch water sampler (required due to secondary side cable congestion) ? Arc-flash and safety labeling ? Lifting lugs and jacking pads ? Nameplate per ANSI C57.12.00 4.Electrical Requirements: ? Primary bushings: (6) 200 A load break wells with inserts for (3)LV and (3) 10KV arresters ? Secondary bushings: NEMA spade w/ supports terminals 10holes (3) LV and (1) neutral per ANSI ? Configuration: Radial Feed ? Impedance: Standard ANSI values for 750 kVA ? Taps: 2 x 2.5% (standard 5 position no load tap changer) 5.Protection and Monitoring: The transformer shall include: ? Bayonet fuse with isolation link? Current limiting fuses ? Load break switch (2 position minimum) ? Nitrogen pressure gauge, test port and blanket ? Temperature gauge ? Pressure vacuum gauge ? Liquid level indicator ? Schrader valve Note: All gauges must be visible. 6. Compliance Requirements: The transformer must comply with: ? ANSI/IEEE C57.12 series ? DOE 2016 efficiency standards ? National Electrical Safety Code (NESC) ? National Electrical Code (NEC /NFPA 70) ? UFGS 26 12 19 ? Pad Mounted, Liquid Filled, Medium Voltage Transformers ?American Buy Act ? PCB-free oil certification ? UL Listed 002. Provide Factory routine test Reports Results and documentation as minimum: ? Insulation resistance test ? Winding resistance test ? Turns ratio (TTR) ?Polarity and phase-relation test ? No-load and load-loss test ? Dielectric test ? Excitation test ?Impedance test ? Applied and Induced potential tests ? Leak Test ? Oil quality test (dielectric strength, moisture, interfacial tension) ? Certified As-built drawings ? Certified test report signed by manufacturer ? Installation and OM manuals ? Warranty documentation (minimum 1 year) ? Destination to the federal facility Fort Buchanan, Puerto Rico00934 ? ECD: 40 weeks ? Unit must arrive fully assembled and ready for installation ?Packing slip must include contract number, PO number, and serial number? Minimum 1 year manufacturer warranty covering defects in equipment. | 73% | Combined Synopsis | 07/29/2026 |
Pad Mount Transformer | 73% | Combined Synopsis | 03/30/2026 |