Annual Medical Gas Inspection and Repairs
Archived on November 11, 2025. Original response deadline: . Full description on SAM.gov.
Overview
- Response deadline
- 3:00 PM CDT
- Posted
- October 16, 2025
- Notice type
- Sources Sought
- Set-aside
- Service-Disabled Veteran-Owned Small Business Set Aside
- NAICS
- 811310: Commercial and Industrial Machinery and Equipment (except Automotive and Electronic) Repair and Maintenance
- Agency
- Department of Veterans Affairs
Notice details
- Office
- 255-NETWORK CONTRACT OFFICE 15 (36C255)
- Place of performance
- Kansas City, Missouri, 64128
- Last updated
- Nov 7, 2026
- First published
- Last updated on SAM.gov
Identifiers
- Solicitation number
- 36C255-26-AP-0313
- Notice ID
- 873395118eeb4bc5ac78ae43fef4b584
Description
Annual Medical Gas/Vacuum Inspection, Certification and Repairs
Kansas City, VA Medical Center
General Information
1. GENERAL: This is a non-personal services contract to provide Annual Medical Gas/Vacuum Inspection, Certification and Repairs for the KC VAMC. The Government shall not exercise any supervision or control over the contract service providers performing the services herein. Such contract service providers shall be accountable solely to the Contractor who, in turn is responsible to the Government.
1.1 Description of Services/Introduction: The Contractor shall provide all personnel, equipment, supplies, facilities, transportation, tools, materials, supervision, and other items to perform Inspection, testing services and Repairs as defined in this Performance Work Statement (PWS), section 5. The Contractor shall perform to the standards in this contract.
The contractor shall have documented experience with projects of similar scope, size and magnitude as the Kansas City VA Medical Center. Contractors will provide documentation on past performance for the previous 5 years with their proposal. Failure to provide this documentation will result in the elimination of the proposal for consideration.
1.2 Background: The Medical Gas and Vacuum System in the Medical Center is required to be inspected, at intervals and frequencies, as defined in NFPA 99 Chapter 5 (2024 Edition) and VHA Directive 7515. The Medical Center has: Medical Air Compressors and Vacuums as source equipment; 6 Operating Rooms each with 2 Hill-Rom Ceiling Columns Model EpiCare P680. The facility also has numerous inventories of Medical Gas Outlets/Inlets, Alarm Panels, Zone Valves and piping systems. See Attachment A.
1.3 Objectives:
Contractor will annually inspect and test: Source Equipment; Medical Gas inlet/outlets; Zone Valves; Alarm Panels and other items as defined by NFPA 99 (2024) – 5.1.14.7 Contractor will provide a detailed report, in electronic format, identifying all deficiencies with a clear color photo and a narrative of each deficiency. The contractor will also make recommendations to correct each deficiencies identified. At the completion of the inspections, the contractor will provide certification to the Kansas City VAMC.
1.4 Scope: Contractor will supply all tools, materials, equipment and supervision to perform Annual Medical Gas and Vacuum Inspections. Upon completion of the inspections, the contractor will provide the inspection Certification for the entire system.
Comprehensive inspection of the system will include:
- Medical Air Compressor Packages
- Medical Vacuum Pump Packages
- Instrument Air Compressor Systems
- Area Alarm and Master Alarm Systems
- Zone Valve Boxes
- Outlet and Inlet assemblies
- Any signage required by NFPA 99
Services include:
- Provide a detailed inspection, inventory and count for all medical gas systems and sub-components of the pipeline distribution system.
- The inventory will include clear color photos for each:
- Source equipment compressor or vacuum.
- Master and Area alarm system panels.
- Zone Valve boxes
- Tank manifolds and Oxygen storage system.
- The inventory will include clear color photos for each:
-
- The inspection will include:
-
-
- Compliance with all Category 1 code requirements for all systems, components and sub-components.
- Clear color photos and a detailed narrative for each deficiency observed.
- Recommendations to correct deficiencies.
- An itemized proposal to correct each deficiency.
- An inspection report, in electronic format. The repot shall include”
- Clear color photos of each deficiency observed and the location of the deficiency.
- A detailed narrative of the deficiency that included the NFPA Standard.
- An itemized quote to repair each deficiency. The quote will have the labor and material costs separated.
- Upon completion of the system inspection, a report will be submitted to the contract COR. It will include a photo of each deficiency and the location of the deficiency.
- After the deficiencies are corrected, a follow-up report will be submitted, and it will include side-by-side before and after photos of each deficiency and the deficiency after it was repaired.
- Prior to submitting the report, the contractor will coordinate the format and layout for the report with the contract COR.
-
- Comprehensive testing and inspection of the system will include:
-
- Outlets / Inlets testing criteria
-
-
- Leak detection using a calibrated, ultrasonic leak detector for all accessible and not-in-use Medical Gas and Vacuum Outlets/Inlets.
- Operational flow testing for all accessible and not in use Medical Gas and Vacuum Outlets/Inlets.
- A minimum of 10% of Medical Gas Outlets will be randomly sampled for concentration percentage and purity. The contractor shall document readings and locations of samples taken.
- Operational Flow NFPA 99 (2024 Edition) 5.1.12.4.10
- Medical Gas Outlet Concentration NFPA 99 (2024 Edition) 5.1.12.4.11
-
-
- Alarm Panels and Zone Valve Boxes testing criteria:
-
-
- Confirm proper labeling for areas controlled or monitored by zone valve box assemblies and area alarm panels.
- Test for LED or Audible failure and accuracy of digital sensors on Alarm Panels against recorded source pressure.\
- Test accuracy of pressure and vacuum indicators in zone valve box assemblies.
- Valve Test - NFPA 99 – 5.1.12.4.4
- Zone Valve Labeling - NFPA 99 – 5.1.11.3
- Alarm Panel Labeling and LED Test - NFPA 99 - 5.1.9.1(7) and (4)
- Accuracy of Digital Indicators - NFPA 99 – 5.1.8.1.4
- Pressure and Vacuum Indicators - NFPA 99 – 5.1.8
-
-
- Master Alarm Panel Testing criteria:
-
-
- All required source equipment alarm signals will be tested to ensure that they correctly actuate and are properly labeled for each alarm condition.
- Master Alarm Panel Signals- NFPA 99 – 5.1.9.2.4
- All required source equipment alarm signals will be tested to ensure that they correctly actuate and are properly labeled for each alarm condition.
-
-
- Electrical system for All Medical Gas and Vacuum components.
-
-
- All components will be tested and verified that their electrical components are wired to the Essential Life Safety Branch of the electrical system. VA Staff will assist with this requirement.
- Power verification - NFPA 99 – 5.1.9.1(9)
- All components will be tested and verified that their electrical components are wired to the Essential Life Safety Branch of the electrical system. VA Staff will assist with this requirement.
-
-
- Source Equipment Testing Criteria:
-
-
- All source equipment will be tested for functionality with Category 1 Code requirements.
- All positive pressure gas systems will be tested for pipeline purity at furthest outlet against source content.
- Gas and Vacuum Supply Sources - NFPA 99 – 5.1.12.4.14.2
- Verifier Piping Purity Test- NFPA 99 – 5.1.12.4.8
-
-
- Boom and Manufactured Assemblies, including OR Boom Pendants:
-
-
- Tested annually for leaks. VA staff will assist with this task. This test requires detaching all secondary equipment from each OR area and performing a 10-minute standing pressure test on each system. If any leaks are found, further investigation will need to be carried out to locate the source of the leak. Minor leaks will be documented on the inspection report. Any significant leak(s) will be brought to the attention of the Mechanical Shop Supervisor as soon as possible.
- Manufactured Assemblies Employing Flexible Connections- NFPA 99 5.1.6
- Tested annually for leaks. VA staff will assist with this task. This test requires detaching all secondary equipment from each OR area and performing a 10-minute standing pressure test on each system. If any leaks are found, further investigation will need to be carried out to locate the source of the leak. Minor leaks will be documented on the inspection report. Any significant leak(s) will be brought to the attention of the Mechanical Shop Supervisor as soon as possible.
-
VHA Directive 7515 requires that 10% of outlets be tested for purity. To satisfy this requirement for the Kansas City, VAMC, a full pipeline purity testing for each medical gas system will be tested to confirm that the entire distribution pipeline system meets the requirements for pipeline purity. The contractor will include the testing results in the report upon completion of the annual inspection and testing service.
VHA Directive 7515 requires cross connection verification of 10 percent of the existing outlets annually. Testing cannot be repeated in an outlet until all outlets in the hospital have been tested once.
Contractors will anticipate that there will be 4 separate instances, in which there were minor modifications done to the system that require the contractor to recertify the system. Some examples of a minor modifications are capping off sections of the piping system when outlets have been removed, adding outlets for a new patient room…
The Contractor shall accomplish (Contract Deliverables):
- Inspections:
- Medical Compressors
- Medical Vacuums
- Instrument Air Compressor Systems
- Area Alarms and Master Alarms
- Zone Valve Boxes
- Outlet and Inlet Assemblies
- Required Signage
- Detailed inventory for all system components and sub-components:
- Source Equipment Compressors and Vacuums
- Medical Compressors
- Medical Vacuums
- Instrument Air Compressor Systems
- Area Alarms and Master Alarms
- Zone Valve Boxes
- Outlet and Inlet Assemblies
- Required Signage
- Tank Manifolds and Oxygen Storage System
- Testing:
- Outlets and Inlets
- Area Alarm Panels
- Master Alarm Panels
- Zone Boxes
- Medical Gas components on Electrical Systems
- Source Equipment
- Boom and Manufactured Assemblies
- Detailed inventory listing with clear color photos.
- The format of the report is to be submitted to the COR within 14 calendar days of contract award.
- Detailed inspection report with clear color photos showing all deficiencies observed during the inspection.
- The format of the report is to be submitted to the COR within 14 calendar days of the contract award.
- Medical Gas and Medical Vacuum Certification documentation.
- Emergency and Unscheduled Repairs:
- Due to the critical Life Safety aspect of the Medical Centers Compressors, Vacuums. And Pumps, this contract will have a Contract Line-Item Number (CLIN) designated for urgent and unscheduled repairs. The purpose of this CLIN is for the immediate repair of problems with these pieces of equipment. This CLIN will be used when invoicing, for the repairs outside of the scheduled maintenance service. The initial funding set-aside for this CLIN shall be $25,000. This value shall not be exceeded without the authorization of the Contracting Officer. The contractor, and the COR, shall closely keep a record of the charges applied to this CLIN. The contractor can only invoice against this CLIN for repairs that were identified, quoted, and approved beforehand, in writing, by the COR.
- Contractor will include the $25,000 for the urgent and unscheduled repair CLIN in their proposal. Should funds remain for this CLIN at the end of the contract period of performance, they will be de-obligated and not invoiced
- Authorization Process for Urgent and Emergency repairs needing immediate attention:
- The costs for all Service Calls and Emergency Service will be invoiced against CLIN.
- Unscheduled service is when a failing component has been identified while doing scheduled services. In this occurrence, the contractor will contact the COR and explain the problem before any additional repairs are made. The COR will verify the issue and then request a brief SOW and a cost proposal from the contractor. Upon agreement of the proposal, the repairs will be authorized by the COR. Once the repairs have been completed, these costs will be applied to the CLIN for urgent and unscheduled service.
- All components of the equipment assemblies are included in this SOW. This includes flexible piping section(s) from the equipment to the Medical Centers’ piping system(s), and the electrical supply and control components. Any failing or failed components will either be repaired and/or replaced. Any equipment and/or components deemed beyond economic repair will be replaced with new equipment that is equal to, or superior of, the existing. This includes the repair/replacement of components due to metal fatigue, rust, and/or physical/environmental damage.
- Service Calls:
- All service calls for repairs will be applied (invoiced) to the CLIN for urgent repairs.
- Contractors will provide the costs of their standard and any premium hourly rates, in their proposal.
Service Representation and Emergency Response Time:
- Contractor shall:
1) Have a 24/7/365 on-call system. There shall be a local telephone number for 24-hour service requests. Calls for service will go to a live representative and will not be automated.
2) Maintain an on-call system of mandatory escalation to management.
3) Respond to calls for emergency service, via telephone, within 1 (one) hour.
4) Have a qualified service technician on site, at the Kansas City VA Medical Center within 2 (two) hours of initial telephone contact by the KCVA.
COR Contract Responsibility
Any task, which cannot be completed as per the SOW, will be communicated to the COR. The contractor will get official directions to resolve any conflicting issues, from the COR and/or Contracting Officer only. The contractor assumes the risk of redoing completed work if they take directions from anyone other than the COR or the Contracting Officer.
Material Receiving:
Contractor will provide all materials at the time of service and/or repairs. No materials will be sent directly to the VA, unless an employee of the contractor is on site to receive and handle the materials. The VA Warehouse staff will not receive sign-for, nor accept responsibility for any contractor materials.
Invoices
All invoices will be sent to the COR for review and concurrence, before they are submitted to Tungsten for payment.
All invoices will have the Contract Line-Item Number (CLIN) for each invoiced item. The CLIN invoiced values will correspond with the CLIN contract values.
-
- Period of Performance: The period of performance for a contract year will be 365 calendar days.
Base Year [2025]
Option Year I [2026]
Option Year II [2027]
Option Year III [2028]
Option Year IV [2029]
1.6 General Information
1.6.1 Federal Observed Holidays:
New Year’s Day Labor Day
Martin Luther King Jr.’s Birthday Columbus Day
President’s Day Veteran’s Day
Memorial Day Thanksgiving Day
Independence Day Christmas Day
1.6.2 Hours of Operation: The Contractor is responsible for conducting business, between the hours of 7:00 AM to 5:00 PM CST Monday through Friday except Federal holidays or when the Government facility is closed due to local or national emergencies, administrative closings, or similar Government directed facility closings. The Contractor must always maintain an adequate workforce for the uninterrupted performance of all tasks defined within this PWS when the Government facility is not closed for the above reasons.
1.6.3 Place of Performance: The work to be performed under this contract will be performed at: The Kansas City VA Medical Center located at 4801 East Linwood Boulevard, Kansas City, Missouri 64128-2226; Jackson County.
1.6.4 Quality Assurance: The government shall evaluate the contractor's performance under this contract in accordance with the Quality Assurance Surveillance Plan (QASP). This plan is primarily focused on what the Government must do to ensure that the contractor has performed in accordance with the performance standards. It defines how the performance standards will be applied, the frequency of surveillance, and the minimum acceptable defect rate(s).
1.6.5 Type of Contract: The Government will award a Firm-Fixed Price contract.
1.6.6 Special Qualifications: All contractor technicians working on KCVA premises completing Annual Inspections and Certification will be Credentialed Medical Gas Verifiers for MGPHO – Medical Gas Professional Healthcare Organization. Additionally, all technicians will have an ASSE 6030 Medical Gas and Vacuum System Verifiers Credential, and ASSE 6035 Bulk Medical Gas Systems Verifier Credential.
1.6.7 Post Award Conference/Periodic Progress Meetings: The Contractor agrees to attend any post award conference convened by the contracting activity or contract administration office in accordance with Federal Acquisition Regulation (FAR) Subpart 42.5. The CO and Contracting Officer’s Representative (COR) shall meet periodically with the contractor to review the contractor's performance. At these meetings the CO will appraise the Contractor of how the Government views the contractor's performance and the contractor will appraise the Government of problems, if any, being experienced. Appropriate action should be taken to resolve outstanding issues.
1.6.9 Contracting Officer’s Representative (COR): The COR Management System Tool (eCOR File)- for nomination, tracking, documentation, and management of CORs will be used. The COR will be identified by separate letter. The COR monitors all technical aspects of the contract and assists in contract administration The COR is authorized to perform the following functions: Assure that the Contractor performs the technical requirements of the contract; perform inspections necessary in connection with contract performance; maintain written and oral communications with the Contractor concerning technical aspects of the contract; issue written interpretations of technical requirements, including Government drawings, designs, and specifications; monitor Contractor's performance and notifies both the CO and Contractor of any deficiencies; coordinate availability of government furnished property, and provide site entry of Contractor personnel. A letter of designation issued to the COR, a copy of which is sent to the Contractor, states the responsibilities and limitations of the COR, especially with regard to changes in cost or price, estimates or changes in delivery dates. The COR is not authorized to change any of the terms and conditions of the resulting order.
1.6.10 Key Personnel: The following personnel are considered key personnel by the Government: [Contracting Officer, Chief FMS, M&O Supervisor, Contract COR and the Mechanical Shop Supervisor]. The Contractor shall provide a contract manager who shall be responsible for the performance of the work. The name of this person and an alternate who shall act for the contractor when the manager is absent shall be designated in writing to the contracting officer. The contract manager or alternate shall have full authority to act for the Contractor on all contract matters relating to daily operation of this contract. Monday through Friday except Federal holidays or when the Government facility is closed for administrative reasons.
Award Overview
Possible prior contract
Inferred, not confirmedInferred, not confirmed. Matched by agency, NAICS, place of performance and end-date proximity. This is a candidate, not the contractor of record.
Dollar amounts are not shown for inferred matches because the link is heuristic. Open the award below to check it.
Contacts
Contracting Officer
Primary Contact
Documents
Files (1)
- Download
P02-Sources Sought Annual Gas Inspection.docx
64 KBAdded in Sources Sought version 3Posted
Lifecycle
- 3Version 3Sources SoughtArchivedCurrent
Annual Medical Gas Inspection and Repairs
- 6Version 6PresolicitationArchived
Type changed from Sources Sought to Presolicitation
Annual Medical Gas Inspection and Repairs
- 9Version 9SolicitationArchived
Type changed from Presolicitation to Solicitation
Annual Medical Gas Inspection and Repairs
Similar Opportunities
Title | Match | Phase | Deadline |
|---|---|---|---|
This is a SOURCES SOUGHT ANNOUNCEMENT ONLY. It is neither a solicitation announcement nor a request for proposals or quotes and does not obligate the Government to award a contract. Requests for a solicitation will not receive a response. Responses to this-- sources sought announcement must be in writing. The purpose of this sources sought announcement is for market research to make appropriate acquisition decisions and to gain knowledge of potential qualified Service-Disabled Veteran Owned Small Businesses, Veteran Owned Small Businesses, 8(a), HubZone and other Small Businesses interested and capable of providing the services described below. Documentation of technical expertise must be presented in sufficient detail for the Government to determine that your company possesses the necessary functional area expertise and experience to compete for this acquisition. Responses to this notice shall include the following: (a) company name (b) address (c) point of contact (d) phone, fax, and email (e) Unique Entity ID (f) Cage Code (g) Tax ID Number (h) Type of small business, e.g. Services Disabled Veteran Owned small Business, Veteran-owned small business, 8(a), HUBZone, Women Owned Small Business, Small disadvantaged business, or Small Business HUBZone business and (i) must provide a capability statement that addresses the organizations qualifications and ability to perform as a contractor for the work described below. The Loma Linda VA Health Care System (LLVAHCS) located at 11201 Benton St. Loma Linda, CA 92357 is seeking a potential qualified contractor that can provide: Medical Gas Inspection. Important information: The Government is not obligated to/nor will it pay for or reimburse any costs associated with responding to this sources sought synopsis request. This notice shall not be construed as a commitment by the Government to issue a solicitation or ultimately award a contract, nor does it restrict the Government to a particular acquisition approach. The Government will in no way be bound to this information if any solicitation is issued. The VA is mandated by Public Law 109-461 to consider a total set-aside for Service-Disabled Veteran Owned Small Business set aside. However, if response by Service-Disabled Veteran Owned Small Business firms proves inadequate, an alternate set-aside or full and open competition may be determined. No sub-contracting opportunity is anticipated. The North American Classification System (NAICS) code for this acquisition is 811310 Commercial and Industrial Machinery and Equipment (except Automotive and Electronic) Repair and Maintenance $12.5 Million. *******DRAFT*******DRAFT******DRAFT*******DRAFT******* D.1 STATEMENT OF WORK TITLE: VA Loma Linda Healthcare System s (VALLHCS) Annual Med Gas Inspection BACKGROUND INFORMATION: VA Loma Linda Healthcare System s (VALLHCS) requires a new maintenance and inspection contract for Medical Gas Distribution System. The Medical gas distribution system must undergo routine source and pipeline system inspections and maintenance to ensure continuous patient safety. PARTS and EQUIPMENT LIST: PARTS QUANTITY OBJECTIVES: VA Loma Linda Healthcare System s (VALLHCS) Medical gas distribution system inspections shall comply with NFPA99 (Health Care Facilities Code), OSHA Life safety fire code, and the ASSE 6000 standard. They require annual central supply checks, routine alarm tests, and specialized third-party inspections by certified ASSE 6020 Inspectors. The services performed shall conform to industry standards and this statement of work (SOW) and lockout and tagout procedures are to be done according to (OSHA Standard29 CFR 1910.147) VA Loma Linda Healthcare systems Policies and Regulations. SCOPE: Contractors shall provide all labor, personnel, supplies, equipment, tools, materials, supervision and other necessary items. Inspection, testing and verification are mandatory for medical gas work and will be performed by licensed ASSE 6020 Medical Gas Inspectors and ASSE 6030 Medical Gas Verifiers. Contractor shall perform Annual Medical Gas Distribution System Inspection on all Sources, Alarms, Zone Valves, and Patient Terminal Outlets / Inlets and bulk oxygen system. Including Areas as follows: Main Hospital First Floor: CLC, CLC Palliative Care, CLC Rehab, 1SW, Mod 3, Emergency department, Second Floor: ICU: 2SW, 2SE, Third Floor: OR 1 through 8, 3F-14, 3F-16, 3D-72, Recovery Room, SICU, X-Ray, MRI, Short Stay, G.I. Labs, 3NW, 3NE, 3SW, 3SE Fourth Floor: 4NW, 4NE, 4SW, 4SE, Nuclear Med, Dialysis, Blood Laboratory, Oncology Building 31 Eye Clinic Building 32 Audiology Building 30 List of items provided for inspection: Medical Gas Sources Medical air compressors, vacuum pumps, gas manifolds, and any other device used to deliver medical gases to patients. 1.Inventoried by location. 2.Leak checked and documented. 3.Recommendations to comply with NFPA 99, 2024 edition Health Care Facilities Code. Master Alarm Panels Alarm panels are located at two separate locations throughout the facility. These panels monitor conditions directly from the medical gas sources. 1.Inventoried by location 2.Tested by removing existing pressure switches and other sensing devices to test the actuation points. No interruption of service is necessary if each device is mounted on code compliant demand fittings. 3.Verify proper points are being monitored at each panel. 4.Verify each panel is in the proper location. 5.Verify proper labeling. Area Alarm Panels Alarm panels that are located throughout the facility monitor medical gas pressures for the area only. 1.Inventoried by location. 2.Tested by lowering pressure in each zone for each gas and documenting the alarm point. 3.Verify proper location. 4.Verify proper labeling. Zone Valve Boxes Accessible valves typically found in a corridor covered by a plastic window used mostly for emergency purposes. 1.Inventoried by location. 2.Checked for leakage from packing, flange, and gauge port using oxygen safe leak detector. 3.Verify proper labeling. 4.Verify proper locations. Medical Gas Outlets/Inlets Connection points for each gas are located mostly in-patient areas. 1.Inventoried by location in each room or area inspected left to right and then top to bottom. 2.Complete an operational pressure test on each outlet and document pass/fail. (Test Parameters per NFPA 99, 2024 edition) 3.Check function of outlet/inlet and latching mechanism. 4.Check for leakage with equipment and without equipment attached. 5.Document connection type and outlet/inlet manufacturer. Oxygen Particulate Analysis Particulates are often found in existing medical gas systems due to improper installation methods that were used in the past. 1.Samples are taken on each floor in each building. Medical Air Dewpoint Analysis Moisture is removed from medical air systems at the source. Periodic Analysis of moisture throughout the facility is important to prevent possible contamination. 1.Samples are taken on each floor in each building. 2.A sample will be taken at the medical air source to compare building samples. Emergency Oxygen Supply Connection Box This box is typically mounted on the outside of a facility to facilitate the back feeding of the oxygen system if there is an interruption in service. 1.Inventoried by location. 2.Check existing location for proper compliance. 3.Check existing piping arrangements to ensure proper order of components. 4.Check to make sure box is secured. Testing to ensure all medical gas booms, and columns are leak free Most operating rooms and procedure rooms have some sort of device to help clinical personnel use the medical gases in the middle of the room by the patient. These devices are either medical gas booms or columns. The hoses and threaded connections inside these devices need to be checked periodically to ensure that there are no leaks. 1. All hoses and secondary equipment were removed from the outlets on each boom and column. 2. A test pressure for each system was observed and documented. 3. All medical gas valves were shut over a period of 10 minutes. 4. After the test period of 10 minutes passed the pressure was observed once again. 5. Any pressure drop was recorded. 6. Recommendations will be made to find existing leaks and to make repairs. Facilities responsibility: A. The facility shall coordinate with all departments to notify of the medical gas/vacuum system inspection and or repairs to be completed. B. The facility shall supply Inspecting personnel with facility maintenance personnel to unlock secured areas that have medical gas/vacuum systems, or a master key may also be supplied to complete inspection services. REPORTS: The contractor will annotate compliance with ASSE 6000, 6020 and 6030 Medical Gas specifications and requirements by submitting a detailed PM report to the Contracting Officer s Representative (COR) along with pictures for each equipment, after PM is completed. The reports shall be submitted to COR, within 14 days of work completion. The contractor shall provide additional reports as required by the COR. The contractor s report shall show the information listed below. The report shall contain, at a minimum, any other information required by the COR and all applicable NFPA and Joint Commission and OSHA specifications, the following: Date of P.M. Time of P.M. Identification of the equipment descriptions, manufacturer, and serial number Location of equipment under P.M. or repair Probable cause of repairs Correction action (servicing, repair or replacement) Who was notified? Comments and recommendations. Completion date Contractor shall complete scheduled preventive maintenance service, inspection and repairs to NFPA and Joint Commission and OSHA requirements for the Medical Gas Distribution System. OVER AND ABOVE REPAIR: Upon discovery of over and above repairs or unforeseen requirements, Contractor shall immediately notify the POC. Parts shall not be procured, nor installation or repairs initiated until approval is obtained from the Contracting Officer and appropriate Facilities Staff/POC. Charges for repair, labor and parts shall originate only when required and upon prior approval being granted by the Contracting Officer. Any additional work performed must be by licensed ASSE 6010 Medical Gas System Installers and ASSE 6040 Medical Gas System Maintenance Personnel. PERIOD OF PERFORMANCE: Base Plus Four from performance start date. Work may be scheduled during the day or night (Depending on load demand), Monday thru Friday and/or Saturday thru Sunday. Daytime hours: 6 am to 4 pm Evening hours: 4 pm to 4 am Contractor shall initiate work within 2 weeks of being contacted by the designated Contracting Officer s Point of Contact (POC) or designee. Work shall be scheduled through the POC or designee, who will coordinate with VALLHCS staff. Timelines are subject to change due to VALLHCS operational requirements. PLACE OF PERFORMANCE: VA Loma Linda 11201 Benton St. Loma Linda, CA 92357 LICENSING REQUIREMENTS: Offeror must possess a 30-hour Occupational Safety and Health Administration (OSHA) safety card. ASSE Medical Gas Verifier 6030 ASSE Medical Gas inspector 6020 SPECIFIC REQUIREMENTS: Contractor shall schedule start date with POC or designee five (5) business days in advance. Contactor personnel shall have valid Loma Linda PIV badges before starting work. Contractor shall coordinate energy source LOCK OUT /TAG OUT procedures with VALLHCS Electrical Supervisor before starting work. When work is complete, Contractor shall notify the VALLHCS Electrical Supervisor that energy sources will be restored and require verification. Contractor s supervisor or lead technician are to check in with VALLHCS Electrical Supervisor, or in their absence, with Graphics Control prior to work each day. Contractor shall conform to the following standards, policies, regulations, governing agency, and any other local, state, or Federal guidelines that are not listed here. OSHA 29CFR Regulations, www.osha.gov NFPA 99, www.nfpa.org Chapter 5 Gas and Vacuum Systems 5.1 Category 1 Piped Gas and Vacuum Systems 5.2 Category 2 Piped Gas and Vacuum Systems 5.3 Category 3 Piped Gas and Vacuum Systems ASSE AUTHORIZED SERVICES: Only those services specified herein are authorized under this contract. Before permitting and/or performing any service of a non-contract nature, the Contractor shall advise the CO of the reason (s) for the additional work and/or service. The Contractor is cautioned that only the CO or his/her designee may authorize additional service that are within the scope of this contract and that reimbursement shall not be made unless prior authorization is obtained from the CO. All changes to the contract shall be issued through a contract modification in writing from the CO to the Contractor. DELEGATION OF AUTHORITY: No additional service shall be provided without the approval from the Contracting Officer (CO) or his/her designee of this contract. The Contractor shall not accept any instructions issued by any other person(s) other than the CO or his/her delegated representative acting within the limits of his/her authority. GOVERNMENT-FURNISHED EQUIPMENT (GFE) GOVERNMENT FURNISHED INFORMATION (GFI): No Government equipment will be used by the Vendor. RECOGNIZED HOLIDAYS: The following is a list of all Government recognized holidays: In accordance with 5 U.S.C. 6103, Executive Order 11582 and Public Law 94-97 the following National holidays are observed and for the purpose of this contract are defined as Legal Federal official holidays : New Year s Day: January 1 Martin Luther King s Birthday: Third Monday in January President s Day: Third Monday in February Memorial Day: Last Monday in May Juneteenth Independence Day: June 19 Independence Day: July 4 Labor Day: First Monday in September Columbus Day: Second Monday in October Veterans Day: November 11 Thanksgiving Day: Fourth Thursday in November Christmas Day: December 25 If a holiday falls on Sunday, the following Monday shall be observed as the legal holiday. When a holiday falls on a Saturday, the preceding Friday is observed as a legal holiday by U.S. Government agencies. Also included, would be any other day specifically declared by the President of the United States of America to be a National Holiday. CONTRACTOR EMPLOYEES AND BADGES: Contractor personnel shall present a neat appearance and be easily recognized as Contractor employees. Examples: wearing of distinctive clothing such as uniform, badges, patches, etc. All contractor personnel shall be required to wear VA provided identification (I.D.) badges above the waist at all times while on the VA grounds. Contractor shall be required to coordinate with the COR to obtain the VA provided I.D. badges for all staff. All VA provided I.D. badges shall be returned at the end of the contract or upon completion of service. Failure to wear ID badges may result in removal from any of the VA facilities and/or otherwise referred to Government property. SAFETY AND PPE EQUIPMENT: Personal Protective Equipment shall be provided for each Contractor employee by the Contractor. Possession of weapons are prohibited. SMOKING and VAPING POLICIES: Smoking and vaping are prohibited on Government property. PARKING: It is the responsibility of Contractor personnel to park only in designated parking areas. Parking information is available from the VA Security Service. The VA shall not invalidate or make reimbursement for parking violations of the Contractor's personnel under any circumstances. COMPLAINTS: Contractor shall promptly and courteously respond to complaints within three (3) working days to the COR. Including complaints brought to the contractor s attention by the CO. Contractor shall maintain a written record of all complaints, both written and oral showing the identity of the individual, the nature of the complaint, and contractor s response. Contractor shall permit the Government to inspect the written records of complaints upon reasonable notice from the CO. Notice to potential offerors: All offerors who provide goods or services to the United States Federal Government must be registered in the System for Award Management (SAM) at www.sam.gov. Additionally, all Service-Disabled Veteran Owned Businesses or Veteran Owned Businesses who respond to a solicitation on this project must be certified by the Small Business Administration; Veteran Small Business Certification, (VetCert) https://veterans.certify.sba.gov/. All interested Offerors should submit information by e-mail to: catherine.fernandezpedernera@va.gov . All information submissions to be marked Attn: Catherine Fernandez, Contract Specialist and should be received no later than 10:00 AM PST on September 30, 2026. | 88% | Market Research | 09/30/2026 |
The U.S. Coast Guard Academy in New London, Connecticut, intends to solicit for preventive maintenance, annual inspection, and corrective maintenance services for Government-owned mobile elevating work platforms (MEWPs), including scissor lifts and boom lifts. The Contractor shall furnish qualified competent personnel, labor, supervision, tools, test equipment, transportation, consumables, and quality control necessary to inspect and maintain the equipment in accordance with applicable U.S. Coast Guard Maintenance Procedure Cards, OSHA requirements, ANSI/SAIA A92 standards, original equipment manufacturer specifications, and all other applicable federal, state, and local requirements. Required services include firm-fixed-price annual preventive inspections for scissor lifts and boom lifts, with corrective maintenance, troubleshooting, repair, replacement, and adjustment services to be ordered on a time-and-materials basis through task orders upon Government approval. | 67% | Combined Synopsis | 11/16/2026 |
This is a Sources Sought Notice, and this notice is being issued for market research purposes only. This notice is not a Request for Quotation or Proposal (RFQ/RFP), and a solicitation is not being issued at this time. This notice shall not be construed as a commitment by the Government to issue a solicitation, nor does it restrict the Government to a particular acquisition methodology. The purpose of this notice is to obtain information regarding the availability and capability of all qualified sources to perform a potential requirement. Interested parties are asked to submit capability statement that clearly and convincingly identifies their ability to fulfill the requirements. Industry feedback to the information below is requested to ensure the VA has not created a defacto sole source requirement. The Network Contracting Office (NCO-10) is seeking to identify Service Disabled Veteran Owner Small Businesses (SDVOSB) and/or Veteran Owned Small Businesses (VOSB) to perform the following services at Detroit VA Medical Center: Annual Preventative Maintenance and Support Services for Environmental Management Service (EMS) which consists of the following janitorial equipment: Steam Cleaners, Extractors, Vacuums, Scrubbers, power washers and other similar equipment. Scope: The contractor shall provide all management, tools, supplies, equipment, transportation, and labor to develop and implement a preventative maintenance and repair plan for the janitorial equipment used by the Environmental Management Service (EMS) of VA Michigan Healthcare System Detroit, Michigan (Detroit VA Medical Center). Vendor to inspect equipment to evaluate condition (a complete list will be provided in the subsequent solicitation documents) Service of equipment to ensure optimal performance and maximum service life for the VA Perform all recommended manufacturer maintenance for the equipment Provide parts order list and labor estimates for repairs outside of the scope of the preventative maintenance and support services contract (i.e., misuse or abuse of equipment by VA staff, etc.). The Government requests that interested parties: Failure to provide a capabilities statement and answers to the questions below may result in your response being excluded in the Governments market research and potential set-aside considerations. Submit a statement of capability outlining their firm s capabilities related to this requirement. Capabilities statement shall provide a detailed overview and qualifications to perform the requirement, including past experience with projects similar in scope. All information shall be submitted in MS Word or Adobe PDF format and shall not exceed 10 pages, including all attachments. Each party s submission shall also include the following information: Organization Name Organization Address Point-of-Contact (name, title, address, telephone number, and email) SAM UEI Number Business Socio-Economic statuses (SBA Certifications, etc.) GSA Contract Number (if applicable) Any other pertinent information Answer questions 1-3 below: Failure to provide a capabilities statement and answers to the questions below may result in your response being excluded in the Governments market research and potential set-aside considerations. QUESTION #1: Is your firm interested in providing a fair and reasonable quote for this requirement? Yes / No (choose one) QUESTION #2: Is your firm an SBA Certified SDVOSB and/or VOSB? If so, please provide a copy of VETCERT certification. QUESTION #3: Is your firm an SBA Certified EDWOSB, WOSB, HUB, 8a, SDV? Please provide any additional certifications regarding the socio-economic status of your company including, WOSB, EDWOSB, HUB, 8a, Small Disadvantage Business, Small Business, etc. The applicable NAICS code for this requirement is NAICS 811310 Commercial and Industrial Machinery and Equipment Repair and Maintenance Services with a Small Business Size Standard of $12.5 Million. The Product Service Code is J079 Maintenance, Repair, and Rebuilding of Equipment Cleaning Equipment and Supplies. For informational purposes only, the following Wage Determinations apply to this requirement: No 2015-4839 Rev 32 (Wayne) All businesses are encouraged to respond; however, each respondent must clearly identify their business size and socio-economic category(s) in their capabilities statement. This Sources Sought is only for the purpose of identifying potential sources as part of market research. No Request for Proposal (RFP), Quote (RFQ), or Invitation for Bid (IFB) exists. Responses to this Sources Sought are not quotes, proposals, or bids on which the VA can issue any contract. This Notice is issued for information and planning purposes only and does not itself constitute an RFP, RFQ or IFB. The Government does not intend to award a contract based only on responses to this Sources Sought. Responses will not be returned. Responders are solely responsible for all expenses associated with responding to this Sources Sought; the VA will not pay for information received in response. Do not submit pricing information in response to this Sources Sought. Failure to provide a capabilities statement and answers to the questions above may result in your response being excluded in the Governments market research and potential set-aside considerations. Detailed capabilities statement and answers to questions 1-3 must be submitted by email to Contracting Specialist Venkatlekhith Muntha at Venkatlekhith.Muntha@VA.gov in an electronic format (email), no later than 1:30 PM EST on (10/20/2026). Responses email subject line shall be the following: 36C25025QXXXX - (Vendor Name) - Response to Sources Sought. All submissions must be in either Word or Adobe PDF format and shall not exceed 10 pages total. | 67% | Market Research | 10/20/2026 |
The Cincinnati Veterans Administration Medical Center (VAMC) has a requirement to provide repairs to generator operation to address failed generators & associated paralleling switchgear. The intention of this Sources Sought is to obtain information only. Please do not send a proposal. Requested information: To aid acquisition planning, we re seeking capable and interested firms for the information requested. If your firm meets the criteria please send the point of contract (ronald.heidemann@va.gov) the following, via email: Firm s Name Socio-Economic Status Whether or not your company has a contract vehicle we can order against If your company believes there is an alternative NAICS code please provide this If your company has any questions please provide. Contract Title. Repair Emergency Power Phase 2 Background. The chosen contractor shall provide repairs to generator operation to address failed generators & associated paralleling switchgear at the Cincinnati VAMC. The fulfillment of the project will allow for testing & repairs/replacement of existing equipment as required to restore full emergency backup generator functionality at this facility. Additional repairs required were identified by ABB during the initial repair of paralleling switchgear and the report is on the last page. Scope. The scope of this contract is to provide recommended repairs for both of the generators at Building #1. This system is currently functioning with only one generator, leaving the facility vulnerable in the event of a power failure at this site. Key task is to restore full emergency backup power for the facility to facilitate repairs of the existing equipment. Key task is test emergency power system and verify it works as intended. Specific Tasks. Maintain emergency generator availability for the facility Maintain security of the generator/switchgear room during the entire project. Work on generators can only be performed on weekend with prior coordination with the VA. Work will need to be done on two separate weekends, one weekend per generator work. Provide required repairs for the associated paralleling switchgear system per diagnose reports from ABB which includes Saturday work. Work includes the following items as identified in the ABB repair report: Replace two damaged MFR13 and reverse power relay to new protective relay and all installation/testing for both generators. Programming changes required for these replacement relays to ensure proper system functionality. Door modification to support the installation and operation of the upgraded relays. Wiring modifications to accommodate the replaced relays. Changes to the existing ABB systems drawings for these replaced relays. The General Contractor (GC) must coordinate as needed with the VA COR for testing of the generator control panels. Two new control panels (one per generator) have been installed. One control panel has been tested and verified to function as intended. The control panel on the inoperable generator requires testing and verification to ensure proper functionality. GC must provide a load bank for testing of both Generator 1 and Generator 2 on this day. 125% of load bank required. GC/subcontractor for paralleling gear work must test paralleling both Generator 1 (1500kW, 3 PH, 4W, 480Y/277V) and Generator 2 (1500kW, 3 PH, 4W, 480Y/277V) and verify it works with the 125% load bank. GC and subcontractor for paralleling gear must change priority of generators to verify they come back online/and shed as designed. GC and subcontractor for paralleling gear must provide a complete testing of the emergency power system including both generators and paralleling switchgear after all repair work is completed and verify it works as intended. Performance Monitoring Contract supervision will be conducted by the Project Section of Engineering Service at the Cincinnati VA Medical Center. Inspection will be made throughout the project and delivery and installation. Security Requirements  7.1 The C&A requirements do not apply and a Security Accreditation Package is not required  Cincinnati VA Medical Center (CVAMC) Record Management Clause.  1. Contractor shall comply with all applicable records management laws and regulations, as well as National Archives and Records Administration (NARA) records policies, including but not limited to the Federal Records Act (44 U.S.C. chs. 21, 29, 31, 33), NARA regulations at 36 CFR Chapter XII Subchapter B, and those policies associated with the safeguarding of records covered by the Privacy Act of 1974 (5 U.S.C. 552a). These policies include the preservation of all records, regardless of form or characteristics, mode of transmission, or state of completion.   2. In accordance with 36 CFR 1222.32, all data created for Government use and delivered to, or falling under the legal control of, the Government are Federal records subject to the provisions of 44 U.S.C. chapters 21, 29, 31, and 33, the Freedom of Information Act (FOIA) (5 U.S.C. 552), as amended, and the Privacy Act of 1974 (5 U.S.C. 552a), as amended and must be managed and scheduled for disposition only as permitted by statute or regulation.   3. In accordance with 36 CFR 1222.32, Contractor shall maintain all records created for Government use or created in the course of performing the contract and/or delivered to, or under the legal control of the Government and must be managed in accordance with Federal law. Electronic records and associated metadata must be accompanied by sufficient technical documentation to permit understanding and use of the records and data.   4. Cincinnati VA Medical Center (CVAMC) and its contractors are responsible for preventing the alienation or unauthorized destruction of records, including all forms of mutilation. Records may not be removed from the legal custody of CVAMC or destroyed except for in accordance with the provisions of the agency records schedules and with the written concurrence of the Head of the Contracting Activity. Willful and unlawful destruction, damage or alienation of Federal records is subject to the fines and penalties imposed by 18 U.S.C. 2701. In the event of any unlawful or accidental removal, defacing, alteration, or destruction of records, Contractor must report to CVAMC. The agency must report promptly to NARA in accordance with 36 CFR 1230.  5. The Contractor shall immediately notify the appropriate Contracting Officer upon discovery of any inadvertent or unauthorized disclosures of information, data, documentary materials, records or equipment. Disclosure of non-public information is limited to authorized personnel with a need-to-know as described in the Statement of Work. The Contractor shall ensure that the appropriate personnel, administrative, technical, and physical safeguards are established to ensure the security and confidentiality of this information, data, documentary material, records and/or equipment is properly protected. The Contractor shall not remove material from Government facilities or systems, or facilities or systems operated or maintained on the Government s behalf, without the express written permission of the Head of the Contracting Activity. When information, data, documentary material, records and/or equipment is no longer required, it shall be returned to CVAMC control or the Contractor must hold it until otherwise directed. Items returned to the Government shall be hand carried, mailed, emailed, or securely electronically transmitted to the Contracting Officer or address prescribed in the Statement of Work. Destruction of records is EXPRESSLY PROHIBITED unless in accordance with Paragraph (4).  6. The Contractor is required to obtain the Contracting Officer's approval prior to engaging in any contractual relationship (sub-contractor) in support of this contract requiring the disclosure of information, documentary material and/or records generated under, or relating to, contracts. The Contractor (and any sub-contractor) is required to abide by Government and CVAMC guidance for protecting sensitive, proprietary information, classified, and controlled unclassified information.  7. The Contractor shall only use Government IT equipment for purposes specifically tied to or authorized by the contract and in accordance with CVAMC policy.   8. The Contractor shall not create or maintain any records containing any non-public CVAMC information that are not specifically tied to or authorized by the contract.   9. The Contractor shall not retain, use, sell, or disseminate copies of any deliverable that contains information covered by the Privacy Act of 1974 or that which is generally protected from public disclosure by an exemption to the Freedom of Information Act.   10. The CVAMC owns the rights to all data and records produced as part of this contract. All deliverables under the contract are the property of the U.S. Government for which CVAMC shall have unlimited rights to use, dispose of, or disclose such data contained therein as it determines to be in the public interest. Any Contractor rights in the data or deliverables must be identified as required by FAR 52.227-11 through FAR 52.227-20.  11. Training. All Contractor employees assigned to this contract who create, work with, or otherwise handle records are required to take VHA-provided records management training. The Contractor is responsible for confirming training has been completed according to agency policies, including initial training and any annual or refresher training.   [Note: To the extent an agency requires contractors to complete records management training, the agency must provide the training to the contractor. TMS Course 10203, VA Privacy & Information Security Awareness will be used to satisfy this requirement.    12. The Contractor shall incorporate the substance of this clause, its terms and requirements including this paragraph, in all subcontracts under this Statement of Work and require written subcontractor acknowledgment of same.   13. Violation by a subcontractor of any provision set forth in this clause will be attributed to the Contractor.  Government-Furnished Equipment (GFE)/Government-Furnished Information (GFI). None. Other Pertinent Information or Special Considerations. a. Identification of Possible Follow-on Work. None. b. Identification of Potential Conflicts of Interest (COI). None. c. Identification of Non-Disclosure Requirements. None. d. Packaging, Packing and Shipping Instructions. None e. Inspection and Acceptance Criteria. Project COR to conduct the final acceptance of satisfactory installation. Risk Control None Place of Performance. This product will be used at the Cincinnati VAMC, specifically within the generator and electrical rooms. Period of Performance. 90 calendar days including equipment/material lead time. Delivery Schedule. TBD Technical/Administrative Requirements Contracted work shall be conducted in accordance with the below VA Specifications. Warranty Contractor must provide a one (1) year warranty to include all materials and labor. ABB Report Julie, After reviewing the project requirements and available options, it has been determined that the only viable solution is to upgrade the MFR13 Relay. The upgrade is expected to be more expensive than originally anticipated because the scope of work extends beyond simply replacing the relay. The upgrade will also require: Programming of the upgraded relay to ensure proper system functionality. Door modifications to support the installation and operation of the upgraded relay. Wiring modifications to accommodate the upgraded relay Changes to the existing systems drawings for the upgrade. Due to these additional labor and material requirements, the total project cost will be higher than our initial estimate. While this was not anticipated as the solution, these modifications are necessary to ensure the system functions properly. Please let us know if you would like us to prepare a quote outlining the additional costs associated with this work for your review. I believe a similar quote was provided in 2025 for the relay upgrade. If you have any questions or would like to discuss the project in more detail, please feel free to reach out. Thanks, Brian Bednar Area Field Service Project Manager Mobile: 984-303-5371 fred.ervin@us.abb.com | 66% | Market Research | 10/21/2026 |
N4008527Q0002-Annual Tank Inspections at Naval Weapons Station Earle, Colts Neck, New Jersey This notice is being issued strictly for Market Research, information and planning and purposes only and shall not be construed as either a solicitation or obligation or commitment on the part of the Government. There will not be a solicitation, specifications, or drawings available at this time. The purpose of this Sources Sought is to help The Department of the Navy, Naval Facilities Engineering Systems Command (NAVFAC), Naval Weapons Station Earle (NWSE), understand industry best practices and sources capable of meeting the requirements detailed by this announcement. NWSE welcomes responses from all interested parties; however, no decision or award of contract will be made based on responses from industry. NWSE will not pay for the preparation of, nor the subsequent use of information submitted in response to this Sources Sought. Respondents will not be notified of the outcome of NWSE’s review of the information received. Additionally, NWSE does not intend to hold discussions concerning this Sources Sought with any interested parties, but reserves the right to contact contractors if additional information is required for clarifications as it pertains to this request for information (RFI). Requirement: NWSE intends to contract for Annual Tank Inspection and Repair Service Calls for approximately 40 above ground fuel tanks, 9 drum storage areas, 4 mobile truck tanks, 1 underground UST tank located at various locations throughout NWSE. The Contractor shall provide all materials and services to test, calibrate, adjust and cathodic protection, automatic tank gauging and fuel management systems on above-ground tank, underground tanks (to include piping) piers and quay walls and associated equipment. To that end, NWSE seeks to gather information about sources able to meet this requirement. The NAICS Code for this requirement is 811310 - Commercial and Industrial Machinery and Equipment (except Automotive and Electronic) Repair and Maintenance. The associated small business size standard for this industry is $12,500,000.00. Instructions to Contractors: All interested contractors are encouraged to submit a response clearly demonstrating their capability to perform this requirement. Proposals are not being requested at this time. Responses to this Sources Sought cannot be considered as offers and cannot be accepted by the Government to form a contract. No formal solicitation exists at this time and no set-aside decision has been made. Responses to this Sources Sought should include the following information: 1. Title of the requirement; Company Name; Address; and Point of Contact (POC) name, phone number, and email address. 2. Company profile to include office location(s), DUNS number/CAGE Code, NAICS, and a statement regarding current small business status to include small business type(s)/certification(s) such as: 8a, WOSB, EDWOSB, HUBZone, SDVOSB, etc. 3. Specific experience (private and/or government) in New York, New Jersey, Pennsylvania, and/or Connecticut performing tank inspection, and repair building, utility, and general tank inspection services under the United Facilities General Specifications (UFGS). Statements should describe the dollar value, indicate whether your firm acted as the prime or subcontractor, list a customer Point of Contact with phone number, and provide description of the experience and how the referenced experience relates to the services described herein. A maximum of five (5) project examples reflecting the firm's experience should be submitted. Please submit responses by 16 November 11:00AM EST directly to James Martin, Contracting Officer, via email at james.j.martin3.civ@us.navy.mil. Please reference the solicitation number and title in the subject of your message. Please limit your responses to standard documents (i.e. Microsoft Office, Adobe PDF, etc.). Do not send compressed (I.e. .zip or .exe extension) or other file types, as they will be stripped from your message. | 65% | Market Research | 11/16/2026 |
Additional Details
Solicitation Number
36C255-26-AP-0313
Archive Date
Nov 11, 2025
Office Address
LEAVENWORTH, KS, 66048