1.The 76th AMXG/567th is requesting utilization of funds for the purchase of one (1) Portable ResistiveLoad Bank.
2.The requested equipment item description / Specifications are outlined below.
a.Quantity of one (1) Portable Resistive Load Bank.
(1)230VAC L-N, 400VAC L-L, 3-Phase, 400 Hz
(2)6-Pin Aircraft Power Receptacle with Shield
(a)Must be supplied in accordance with (IAW) the requirements specified in DrawingLE409-0001.
(b)Suggested sources of supply (Anderson Airmotive part no. 3-498501 OR ITT CannonEA376 IAW dwg. LE409-0001).
(3)Load capacity of 100 kW or more.
(4)Switch to load in increments of 10 kW or less.
(5)Meter to display input frequency, volts, amps, watts.
(6)E/F interlock.
(7)4x BNC female connectors for monitoring of input power voltage, current, and frequency perphase with oscilloscope.
(8)Thermal Protection.
(9)Casters for ease of transport.
(10)Lifting pockets for loading/unloading with forklift.
(11)Noise level not to exceed 85 dB (A) IAW OSHA standard 29 CFR 1910.95.
Overview
Award Overview
Possible prior contracts
Sign in to see possible prior contracts for this requirement (matched by agency, NAICS and place of performance; not confirmed).
Contacts
Contracting Officer
Primary Contact
Secondary Contact
Documents
No documents available.
Lifecycle
A26-034- Pre-Solicitation
Formal solicitation typically follows within 30–60 days. (estimate)
Similar Opportunities
Title | Phase | Agency | NAICS | Set Aside | Posted | Deadline | Location |
|---|---|---|---|---|---|---|---|
Additional Details
Solicitation Number
A26-034
Archive Date
Feb 21, 2026
Office Address
TINKER AFB, OK, 73145-3303