Correct Electrical Deficiencies

Active, responses due . Full description on SAM.gov.

Overview

Response deadline
10:00 AM EST
Posted
November 4, 2026
Notice type
Solicitation
Set-aside
Service-Disabled Veteran-Owned Small Business (SDVOSB) Set-Aside (FAR 19.14)
NAICS
236220: Commercial and Institutional Building Construction
Agency
Department of Veterans Affairs

Notice details

Office
246-NETWORK CONTRACTING OFFICE 6 (36C246)
Place of performance
Fayetteville, North Carolina, 28301
PSC
6150: MISCELLANEOUS ELECTRIC POWER AND DISTRIBUTION EQUIPMENT
Last updated
Nov 5, 2026
First published
Last updated on SAM.gov

Identifiers

Solicitation number
36C24627B0001
Notice ID
33cea54e56594fd4a20fb45b1905b49a

Description

SOW 
565-22-500 Correct Electrical Deficiencies 
Fayetteville VAMC

Intent
The project consists of correcting electrical deficiencies as noted from previous VA facility assessments. Improvements include; New electrical entrance building, medium voltage loop replacement, replace electrical distribution equipment, ground conductor corrections, incidental electrical equipment cleanup throughout the Fayetteville VAMC, and minor HVAC and Plumbing improvements.  Period of performance 1,174 calendar days.
Medium Voltage
VA owned medium voltage loop and entrance equipment will be modified or replaced with the following scope:
Replace existing medium voltage entrance equipment with new at campus entrance. 
Provide new building:
Slab on grade, brick on CMU wall, Slate roof tile (to match existing facility)
Provide new VA owned medium voltage cables in concrete encased duct bank for medium voltage loop. Approximately 300 .
Demo and remove old VA owned medium voltage entrance metal shack.
Replace medium voltage sectionalized switch. 
Provide new metal-clad switchgear with draw-out vacuum circuit breakers.
Replace medium voltage oil filled transformer (1)
Panel Replacement and Branch Circuit Improvements
Correct deficiencies to electrical panels and branch circuit wiring which are not correctly sized, protected, or are at end of useful life, as identified through various inspections over the years. o 

All work will be phased. All replacements to existing equipment will require the contractor to filled-out a phasing plan for VA approval. All replacements to existing equipment will require a temporary power solution to minimize electrical outage to existing areas. Such deficiencies include:
Replace-in-same-room building entrance and large distribution equipment:
Normal (service entrance) Switchboards: approx. 2 
Generator switchboards: approx. 2 
Automatic transfer switch: approx. 7
Replace-in-place distribution panels and panelboards distribution equipment
Distribution Panels: approx. 5
Panelboards: approx. 68
Replace undersized feeders
Redundant Gound
Provide redundant equipment grounding conductor to a portion of the facility.
Approx. 100,000 square feet of existing electrical branch circuit distribution in occupied space. 
HVAC And Plumbing
Reroute (vertically & horizontally) Sewer piping and hot water piping to avoid electrical room.
Provide exhaust fan to new Medium Voltage building. 
Incidental Electrical Equipment Cleanup
Provide Identification tag to new and existing equipment throughout the facility: approx. 100 tags
Clean debris from existing electrical enclosures throughout the facility: approx. 30 enclosures.
Correct panel grounding, terminate cable directly to existing panel s ground bar: approx. 30 panels.

ALTERNATE NO.1: BASE BID except delete Bldg 1, Floor 1 and Floor 3 of deficiency item 134 which directs the contractor to provide ground conductors in existing conduit. Which is noted on Sheet B01-E200.
 

Full description on SAM.gov

Award Overview

Contacts

Contracting Officer

Primary Contact

Angelo Harris
Contracting Officer

Documents

Files (4)

  • 36C24627B0001.docx

    271 KBAdded in Solicitation version 2Posted
    Download
  • Correct Electrical Deficiencies Specifications.pdf

    3.2 MBAdded in Solicitation version 2Posted
    Download
  • ATTACHMENT - BAA TAA COMPLIANCE CERTIFICATION.docx

    21 KBAdded in Solicitation version 2Posted
    Download
  • 36C24627B0001_1.docx

    16 KBAdded in Presolicitation version 1Posted
    Download

Lifecycle

  1. 1
    Version 1Presolicitation

    6150--Correct Electrical Deficiencies

    Notice 2b09d3389e514695959b6e38457fd6b6 on SAM.gov

  2. 2
    Version 2SolicitationCurrent

    Type changed from Presolicitation to Solicitation

    Correct Electrical Deficiencies

    Notice 33cea54e56594fd4a20fb45b1905b49a on SAM.gov

Similar Opportunities

Additional Details

Solicitation Number

36C24627B0001

Archive Date

Dec 23, 2026

Office Address

HAMPTON, VA, 23667