FY26 750kVA 3-Phase Transformer
Archived on June 27, 2026. Original response deadline: . Full description on SAM.gov.
Overview
- Response deadline
- 12:00 PM CDT
- Posted
- June 4, 2026
- Notice type
- Combined Synopsis/Solicitation
- Set-aside
- Total Small Business Set-Aside (FAR 19.5)
- NAICS
- 335311: Power, Distribution, and Specialty Transformer Manufacturing
- Agency
- Department of WarDepartment of the Air Force
Notice details
- Office
- AIR MOBILITY COMMAND.FA4407 375 CONS LGC
- Place of performance
- Scott Air Force Base, Illinois, 62225
- PSC
- 6120: TRANSFORMERS: DISTRIBUTION AND POWER STATION
- Last updated
- Oct 30, 2026
- First published
- Last updated on SAM.gov
Identifiers
- Solicitation number
- FA440726Q1000
- Notice ID
- 9eeae59c2816404eb92f475aed1e6399
Description
Request the purchase of the product listed below. This acquisition is being procured utilizing NAICS Code 335311 Power, Distribution, and Specialty Transformer Manufacturing: Ballasts Lamp holders, and Starters Size Standard 600 Employees and PSC Code 6120, Transformers: Distribution and Power Station. This requirement will be a Small-Business Set-Aside. Using RFO Part 12 procedures, 375th CONS intends to evaluate submitted quotes using Lowest Price Technically Acceptable (LPTA) criteria, and a single award will be made.
To be considered for award, offerors must have an active registration in SAM. Please provide an offer for the product listed below by: 10:00 A.M. CST 5 June 2026. (All RFQ info and Transformer Specs are attached)
Copper Windings Required - Updated 4Jun26
kVA - 750 kVA 3 Phase Pad-Mount Transformer
Insulating fluid - Envirotemp FR3
Efficiency Standard - DOE 2016
High Voltage - 12470GY/7200 Volts
High Voltage kV Class - 15 kV Class
High Voltage kV BIL - 95 kV BIL
Primary Termination Style - Dead Front
Primary Feed Type - Loop Feed
Taps - 2 - 2.5% taps above and 2 - 2.5% taps below nominal
Tap Changer - 5-position tap changer
Tap Changer Switch Location - Frontplate HV Compartment
High Voltage Bushings - 200 amp Cooper bushing wells with removable studs (Quantity: 6)
Primary Ground Bushing Selection - Combined H0X0 Bushing
High Voltage Inserts - 15 kV, 95 kV BIL load-break inserts (Quantity: 6)
Loadbreak Switch(es) - 15-38 kV, 300A 2-Position (Quantity: 3)
Loadbreak Switch Location - Frontplate HV Compartment
High Voltage Arresters - Varistar elbow arresters, 15 kV class, distribution class 15 kV (Quantity: 3)
Overcurrent Protection Bayonet Fuses in series with Partial-Range Current-Limiting Fuses (Quantity: 3)
Expulsion fuses Bayonet fuses - (Quantity: 3)
Bayonet Holder - Copper Bayonet Fuse Holder (Quantity: 3)
Low Voltage - 480Y/277 Volts
Low Voltage kV Class - 1.2 kV Class
Low Voltage kV BIL - 30 kV BIL
Secondary Termination Style - Live Front
Secondary Feed Type - Radial Feed
Low Voltage Bushing Location - LV Frontplate (seg 1)
Low Voltage Bushings - Integral aluminum 12-hole spade bushing(s) (Quantity: 4)
Bushing Supports - Standard LV Bushing Support Assembly
Cabinet hardware - Penta-head cabinet door bolts
Cabinet Types - IEEE/ANSI Infrared Viewing Windows - No Window Required Bushing Layout - K 4.5 Loop feed per IEEE C57.12.34-2022 Figure 11 minimum dimensions (without bails) Special Paint - Federal Spec Number Sherwin Williams 6006, Black Bean Brown Cabinet Sill Construction - 304L Stainless steel cabinet sill Cabinet Sides Construction - 304L Stainless steel cabinet sides Tank Base Construction - 304L Stainless steel tank base FM / UL Certifications - UL Listed Liquid Level Gauge - Magnetic liquid level gauge Pressure Vacuum Gauges - Pressure/vacuum gauge Thermometer - Thermometer, dial-type Other Fittings - Schrader valve Drain Valve - Drain valve with sampler in LV Compartment (1") Fill Valve - Fill plug in LV Compartment Pressure Relief Device - Pressure relief device, 50 SCFM Ground Pads - Two-hole ground pads (Quantity: 3) Nitrogen Blanket - Yes
Cover Bolted cover
Gauges Location Inside Main Cabinet on Front Plate
Award Overview
Contacts
Contracting Officer
Primary Contact
Secondary Contact
Documents
Files (9)
- Download
Updated 4Jun26_Transformer Specs.docx
29 KBAdded in Combined Synopsis/Solicitation version 6Posted - Download
Amendment 04 - FY26 750kVA 3-Phase Transformer - FA440726Q1000_cao4Jun26.pdf
223 KBAdded in Combined Synopsis/Solicitation version 6Posted - Download
QandA_Updated 04June26_MHW.pdf
67 KBAdded in Combined Synopsis/Solicitation version 6Posted - Download
Amendment 03 - FY26 750kVA 3-Phase Transformer - FA440726Q1000_cao3Jun26.pdf
220 KBAdded in Combined Synopsis/Solicitation version 4Posted - Download
QandA_Updated 03June26_MHW.pdf
63 KBAdded in Combined Synopsis/Solicitation version 4Posted - Download
Amendment 02 - FY26 750kVA 3-Phase Transformer - FA440726Q1000.pdf
217 KBAdded in Combined Synopsis/Solicitation version 3Posted - Download
Amendment 01 - FY26 750kVA 3-Phase Transformer - FA440726Q1000.pdf
192 KBAdded in Combined Synopsis/Solicitation version 2Posted - Download
CLSExport_FA440726Q1000.pdf
22 KBAdded in Combined Synopsis/Solicitation version 1Posted - Download
SAM RFQ.docx
43 KBAdded in Combined Synopsis/Solicitation version 1Posted
Lifecycle
- 1Version 1Combined Synopsis/SolicitationArchived
FY26 750kVA 3-Phase Transformer
- 2Version 2Combined Synopsis/SolicitationArchived
FY26 750kVA 3-Phase Transformer
- 3Version 3Combined Synopsis/SolicitationArchived
FY26 750kVA 3-Phase Transformer
- 4Version 4Combined Synopsis/SolicitationArchived
FY26 750kVA 3-Phase Transformer
- 6Version 6Combined Synopsis/SolicitationArchivedCurrent
FY26 750kVA 3-Phase Transformer
Similar Opportunities
Additional Details
Solicitation Number
FA440726Q1000
Archive Date
Jun 27, 2026
Office Address
SCOTT AFB, IL, 62225-5015