Transformers

Archived on August 7, 2026. Original response deadline: . Full description on SAM.gov.

Description

3 EA pole mounted transformers with the following capabilities:

Transformer Type: Pad Mounted, Compartmental-Type Transformer Configuration: Liquid Filled

- Mounted Transformer Feed Type: Loop Feed

- Operation: Step-Down Operation (Not Approved for Step-Up)

- Phase: Three Phase Capacity: 165 KVA x3 Vector Group: DYN1

- Primary Voltage: 13200Y        

- Primary Voltage Switch: N/A Primary Voltage Class: 15 kV Class Primary Phasor: Delta

- Primary BIL: 95 KV

- Secondary Voltage: 208Y/120 Secondary Voltage Class: TAPS 2.5% A/B

- Secondary BIL:  60 Hz Temperature Rise: 65°C

- Insulation Rating: Class OE Insulation - 120°C, 248°F

- Cooling Class: KNAN; Self-Cooled

- Forced Air (Fans): None

- Tap Changer: 5-position Tap Changer

- Tap %: 2.5%

- Standard warranty

Vendor to provide delivery/freight.

Full description on SAM.gov

Overview

Agency:
Department of WarDepartment of the Air Force
Office:AIR EDUCATION AND TRAINING COMMAND.FA4801 49 CONS PK
Posted:July 29, 2026
NAICS:335311: Power, Distribution, and Specialty Transformer Manufacturing
Last Updated:Aug 21, 2026
PSC:6120: TRANSFORMERS: DISTRIBUTION AND POWER STATION
Set-Aside:Small Business Set Aside - Total
Type:Solicitation
Place of Performance:Holloman Air Force Base, New Mexico, 88330

Award Overview

Possible prior contracts

Sign in to see possible prior contracts for this requirement (matched by agency, NAICS and place of performance; not confirmed).

Contacts

Contracting Officer

Primary Contact

Secondary Contact

Documents

Select documents to download

Showing 4 of 4 items

Document
Source
Agency
Posted Date
File Size
Actions
SolicitationDEPT OF THE AIR FORCEJul 29, 202681.65 KB
SolicitationDEPT OF THE AIR FORCEJul 29, 2026473.76 KB
SolicitationDEPT OF THE AIR FORCEJul 29, 202696.95 KB
SolicitationDEPT OF THE AIR FORCEJul 29, 2026473.75 KB

Lifecycle

Solicitation:FA480126Q0027
  1. Solicitation

Award typically follows within 30–90 days after the response deadline. (estimate)

  1. 2×
    SolicitationCurrentJul 28, 2026

    Transformers

    Notice f3e017370f164f96b69b8c2439fef18a on SAM.gov

Similar Opportunities

Title
Phase
Agency
NAICS
Set Aside
Posted
Deadline
Location
Awarded335311Total Small Business Set-Aside10/16/2026Open0, OK
1000 KVA TRANSFORMER
Combined Synopsis335311Total Small Business Set-Aside09/23/202609/30/2026-
Pad Mount Transformer
Combined Synopsis335311Total Small Business Set-Aside08/25/202608/31/2026-
Provide one Pad Mounted Transformer 750 kVA, 13.2 kV /208Y/120 V. Salient Characteristics: Furnish one (1) pad mounted, dead front, radial transformer, rated: ? Capacity: 750 kVA ? Phases: 3 ? Primary Voltage: 13,200 V (15 kV class) ?Secondary Voltage: 208Y/120 V ? Frequency: 60 Hz ? Phase: Three phase ? Cooling :ONAN ? Fluid: Mineral oil 2. Mandatory Physical Dimensions: The following dimensions are non negotiable: ? Height: 63?� inches (up to 64?� inches) ? Width: 65 inches ? Depth: May varies (existing is 41 inches) The Contractor shall confirm with proposal the manufacturing dimensions, either in writing or by a shop drawing, for government approval. 3. Mechanical and Construction Requirements: The transformer shall include: ?Stainless steel tank, cabinet and hardware (304) ? Dead front construction ? Pentahead security hardware ? ANSI 61 Grey color to match with existing enclosure ? Welded tank construction, sealed and pressure tested ? 1-inch Oil drain valve located on the primary side with 3/8-inch water sampler (required due to secondary side cable congestion) ? Arc-flash and safety labeling ? Lifting lugs and jacking pads ? Nameplate per ANSI C57.12.00 4.Electrical Requirements: ? Primary bushings: (6) 200 A load break wells with inserts for (3)LV and (3) 10KV arresters ? Secondary bushings: NEMA spade w/ supports terminals 10holes (3) LV and (1) neutral per ANSI ? Configuration: Radial Feed ? Impedance: Standard ANSI values for 750 kVA ? Taps: �2 x 2.5% (standard 5 position no load tap changer) 5.Protection and Monitoring: The transformer shall include: ? Bayonet fuse with isolation link? Current limiting fuses ? Load break switch (2 position minimum) ? Nitrogen pressure gauge, test port and blanket ? Temperature gauge ? Pressure vacuum gauge ? Liquid level indicator ? Schrader valve Note: All gauges must be visible. 6. Compliance Requirements: The transformer must comply with: ? ANSI/IEEE C57.12 series ? DOE 2016 efficiency standards ? National Electrical Safety Code (NESC) ? National Electrical Code (NEC /NFPA 70) ? UFGS 26 12 19 ? Pad Mounted, Liquid Filled, Medium Voltage Transformers ?American Buy Act ? PCB-free oil certification ? UL Listed 002. Provide Factory routine test Reports Results and documentation as minimum: ? Insulation resistance test ? Winding resistance test ? Turns ratio (TTR) ?Polarity and phase-relation test ? No-load and load-loss test ? Dielectric test ? Excitation test ?Impedance test ? Applied and Induced potential tests ? Leak Test ? Oil quality test (dielectric strength, moisture, interfacial tension) ? Certified As-built drawings ? Certified test report signed by manufacturer ? Installation and OM manuals ? Warranty documentation (minimum 1 year) ? Destination to the federal facility Fort Buchanan, Puerto Rico00934 ? ECD: 40 weeks ? Unit must arrive fully assembled and ready for installation ?Packing slip must include contract number, PO number, and serial number? Minimum 1 year manufacturer warranty covering defects in equipment.
Combined Synopsis335311Total Small Business Set-Aside07/22/202607/29/2026-
Amended to change NAICS code from 423610 to 335311. 25 KVA POLE MOUNT TRANSFORMER
Combined Synopsis335311Total Small Business Set-Aside04/23/202604/29/2026-

Additional Details

Solicitation Number

FA480126Q0027

Archive Date

Aug 7, 2026

Office Address

HOLLOMAN AFB, NM, 88330-8225